Liebert 6000VA Double-Conversion Online Rackmount 4U UPS, Refurbished (GXT2-6000RT208)
|
Quantity In Stock: 6
Manufacturer: Liebert
Manufacturer Part No: GXT2-6000RT208
|
This is a refurbished Uninterruptible Power Supply/Battery Backup unit. It has been installed with brand new, high quality batteries, and has been thoroughly tested and then professionally packed in a brand new box. All products sold by UPSforLESS are fully covered for all parts and labor by our famous One-Year "No-Hassle" warranty and our innovative 30-Day "Lemon" warranty.
The GXT2 takes the outstanding features and unmatched reliability of the UPStation GXT series and puts it into a smaller 2U cabinet. A true on-line UPS, GXT2 includes power factor correction, frequency conversion, unlimited external battery connectability, and internal automatic / manual bypass capability. For maximum flexibility, the GXT2 can be installed as a space-saving rack-mounted unit or a space-saving, free standing tower. Features:
- True On Line (Double Conversion) Technology
- User replaceable batteries without removing GXT2 from rack
- Wide input voltage window allows UPS support without going to battery, extending systems availability
- Built in Surge Suppression
- SNMPE3 compatible
- External plug and play, 2U battery cabinets available
- Configurable as rack or tower Specifications
Output
- Capacity 6000VA (4200 Watts)
- Nominal Voltage 120/208 VAC
- L1-L2 Factory default output phase angle: 120 Degrees
- Allowable output phase angle: 120, 180 or 240 Degrees, auto-sending on initial application of AC
- Factory default L1-N, L2-N VAC: 120 VAC
- User configurable L1-N, L2-N VAC: 100, 110, 115, 120, 127 VAC +/- 3%
- Output connections:
- (1) L14-30R
- (1) L6-30R
- (4) 5-20R (Standard 120V 3-prong receptacles will also accept 20Amp straight plug also known as âTâ plug)
- Frequency 50/60 Hz
- Waveform Sinewave
Input
- Input Voltage 120/208 VAC at 120 degrees
- Frequency 50/60 Hz
- L1-L2 Input Phase Angle 120 Degrees
- Allowable Input Phase Angle 120, 180, 240 degrees. Auto sensing on application of AC.
- Factory default L1-N, L2-N VAC: 120 VAC Nominal
- User configurable L1-N, L2-N VAC: 100, 110, 115, 120, 127 VAC
- Input power connection: L14-30P
Batteries
- Type Valve-regulated non-spillable, flame-retardant, sealed lead-acid batteries
- Runtime at full load (4200 Watts) 5 minutes
- Runtime at 75% load (3150 Watts) 8 minutes
- Runtime at 50% load (2100 Watts) 14 minutes
- Runtime at 25% load (1050 Watts) 32 minutes
- Runtime at minimal load (420 Watts) 75 minutes
- Replacement battery kit URBC120912
- Recharge Time 6 hours to 90% capacity
- External Battery Cabinet for extended runtime capability GXT2-144VBATT
Physical
- Width 16.9 inches (430 mm)
- Depth 24.2 inches (615 mm)
- Height 6.9 inches (4U) (176 mm)
- Weight 146 lbs. (66.1 Kg)
- Audible Noise <50 dBA at 1 meter from front or sides
Copmpliance
- UL 1778
- c-UL Listed
- FCC Part 15 Subpart B Class A
- IEEE/ANSI C62.41 Category A & B
- ISTA Procedure 1A
|
|