Liebert UpStation 2700VA Double-Conversion Online High Voltage 208 Volt Tower/Rackmount 2U UPS, Refurbished (GXT2-2700RT-208)

Our Price: $849.00
Quantity In Stock: 2
Manufacturer: Liebert
Manufacturer Part No: GXT2-2700RT-208

This is a refurbished Uninterruptible Power Supply/Battery Backup unit. It has been installed with brand new, high quality batteries, and has been thoroughly tested and then professionally packed in a brand new box. All products sold by UPSforLESS are fully covered for all parts and labor by our famous One-Year "No-Hassle" warranty and our innovative 30-Day "Lemon" warranty.

Note: This is a high voltage 208 volt uninterruptible power supply. It is designed for use in North America and requires special plugs and circuits. Please make sure that you do require uninterrupted power for 208V equipment before ordering this battery backup.

The GXT2 takes the outstanding features and unmatched reliability of the UPStation GXT series and puts it into a smaller 2U cabinet. A true on-line UPS, GXT2 includes power factor correction, frequency conversion, unlimited external battery connectability, and internal automatic / manual bypass capability. For maximum flexibility, the GXT2 can be installed as a space-saving rack-mounted unit or a space-saving, free standing tower.

Features:

  • True On Line (Double Conversion) Technology
  • User replaceable batteries without removing GXT2 from rack
  • Compatible with Intellislot OCWEBCARD Card
  • Compatible with RELAYCARD-INT (relay contacts)
  • Compatible with USBCARD
Input
  • NEMA L6-20 208 Volt, single-phase.
Output
  • 208 Volt 60/50 Hz, single-phase, 2-wire-plus-ground (Configurable for 220/230/240 Volt)
  • Output Power 2700 VA/1890 Watts
  • Receptacles (1) NEMA L6-20, (2) NEMA L6-15
Battery
  • Battery Recharge: The UPS contains a battery recharge rate designed to prolong battery life. Recharge time for UPS internal batteries is five (5) hours maximum to 95% capacity after a complete discharge into full load.
Surge Protection
  • Electrostatic Discharge: The UPS is able to withstand an electrostatic discharge compliant to ENC61000-4-2, level 4, for 120 VAC, 208 VAC, and 230 VAC units (15 kV through air, 8 kV contact) without damage and will not affect the connected load
  • MOVs will be rated 300 Volt, 150 Joules minimum connected L-G and N-G.
Environmental
  • Ambient Temperature Operating: 0 C to +40 C (+ 32 F to + 104 F) for altitudes 0 to 1500 meters (0 to 5,000 ft.) above sea level.
  • Audible Noise generated by the UPS under normal operation does not exceed 50dBA when measured at 1 meter from the surface of the UPS.
Physical
  • Height 3.47 inches
  • Depth 27.2 inches
  • Width 16.9 inches
  • Weight 75.2 lbs
System Indicators
  • The "Fault" LED indicator illuminates red to indicate a UPS fault condition.
  • The "Battery" LED indicator illuminates amber to indicate the UPS is operating from battery power.
  • The "Bypass" LED indicator illuminates amber to indicate the UPS is operating on Bypass power.
  • An audible alarm is provided and activated by any of the above alarm conditions.
  • The "UPS ON" LED indicator illuminates green to indicate the UPS inverter is operating and supplying power.
  • The "AC Input" LED indicator illuminates green to indicate the UPS is operating from utility / mains power.
Communications
  • The UPS contains a DB9F (9 pin female) connector on the rear panel to allow UPS status communications to a computer system. The DB9F contains photo couplers to signal on battery and low battery operational status.

Related Products